Technical data
|
|
|
Rated capacitance
|
CN
|
3×121.9μF
|
Tolerance
|
|
±5%
|
Rated voltage
|
UN(Line voltage)
|
3300V.AC
|
Rated frequency
|
Fn
|
60Hz
|
Output
|
Qn
|
500kvar
|
Maximum current
|
Irms
|
3×87.5A
|
Maximum peak current
|
Î
|
3×6KA
|
Maximum surge current
|
Is
|
3×18KA
|
Series resistance
|
Rs
|
3×5mΩ
|
Tangent of the loss
|
tanδ
|
0.002(100Hz)
|
Tangent of the loss angle
|
tanδ0
|
0.0002
|
Self discharge time const.
|
C × Ris
|
10000S
|
Self inductance
|
Le
|
≤120nH
|
Lowest operating temperature
|
Θmin
|
-40°C
|
Maximum operating temperature
|
Θmax
|
70°C
|
Storage temperature
|
Θstorage
|
-40°C~70°C
|
Service life
|
at Θhotspot
|
100000 h(<70 °C)
|
Failure quota
|
|
100Fit
|
|
|
|
Test data
|
|
|
Voltage test between terminals
|
Vtt
|
2.15UN/10S
|
A.C. voltage test terminal/container
|
Vt-c
|
8000V.AC/60S
|
|
|
|
Operating altitude
|
|
2000m(max)
|
|
accessories:
Over Voltage
|
1.1Un(30% of on-load-dur) |
System adjustment
|
1.15Un(30min/day) |
1.2Un(5min/day) |
1.3Un(1min/day) |
System Switch
|
1.5Un(100ms every time,1000times during the lifetime) |
Permitted torque
M6 Internal thread
|
4.5Nm
|
|
M8 Internal thread
|
6Nm
|
|
M8 external thread
|
6Nm
|
|
M10 external thread
|
8.5Nm
|
|
M12 external thread
|
15.5Nm
|
|